2.4.3
Set up Westinghouse Model TC200 veritrim electronics
Before beginning operation, it is important to change the probe heater setpoint of the
existing electronics to support the Rosemount
™
Oxymitter DR In-Situ Oxygen Probe.
To convert the Model TC200 Electronics Package for use with the Rosemount Oxymitter
DR probe, an EPROM change is necessary. The replacement EPROM needed is part number
1M0315G02.
Replace EPROM
Procedure
1. Shut off and lock out power to the electronics package.
2. Open electronics enclosure.
3. On the main PCB, locate and remove old EPROMs, U11 and U12.
Figure 2-18: Main PCB (Model TC200) EPROM Replacement
4. Replace with new EPROMs (part number 1M03154G02), being careful to install U11
and U12 in their proper locations.
5. Close electronics enclosure and power up system.
Reference Manual
Install
00809-0100-4880
October 2019
Rosemount Oxymitter DR
45