Figure 2-12: Installation with Drip Loop and Insulation Removal
A. Line voltage.
B. Logic I/O 4-20 mA signal.
C. Drip loop.
D. Stack or duct metal wall.
E. Mounting plate.
F. Insulation.
G. Replace insulation after installing Rosemount Oxymitter 4000.
4. If the system has an abrasive shield, check the dust seal gaskets. Make sure the
joints in the two gaskets are staggered 180 degrees and that the gaskets are in the
hub grooves as the transmitter slides into the 15 degree forcing cone in the abrasive
shield.
Note
If process temperatures will exceed 392 °F (200 °C), use anti-seize compound on the
stud threads to ease future removal of the transmitter.
5. Insert probe through the opening in the mounting plate and bolt the unit to the
plate.
Note
To maintain CE compliance, ensure a good connection exists between the
mounting plate studs or earthing screws on electronics housing and earth.
Reference Manual
Install
00809-0100-4880
October 2019
Rosemount Oxymitter DR
35