2.1.2
Install probe
You may install the Rosemount
™
Oxymitter 4000 intact, as you have received it.
Prerequisites
Ensure all components are available to install the transmitter. If equipped with a ceramic
diffuser, make sure the diffuser is not damaged.
Note
Emerson recommends an abrasive shield for high velocity particulates in the flue stream
(such as those in coal-fired boilers, kilns, and recovery boilers).
Procedure
1. Weld or bolt mounting plate onto the duct.
2. If using the optional ceramic diffusion element, make sure to correctly orient the
vee deflector. Before inserting the transmitter, check the direction of the flow of
gas in the duct. Orient the vee deflector so the apex points upstream towards the
flow.
a) Loosen the setscrews.
b) Rotate the vee deflector to the desired position.
c) Retighten the setscrews.
Install
Reference Manual
October 2019
00809-0100-4340
48
Emerson.com/Rosemount