Table 7-1: Logic I/O Configuration (as Set at HART/AMS or LOI)
(continued)
Mode
Configuration
4
The unit is configured for a High AC Impedance.
Calibration recommended
.
The unit is configured for both a Unit alarm and a High AC Impedance.
Calibration
recommended
.
6
The unit is configured for both a Low O
2
and High AC Impedance.
Calibration
recommended
.
7
The unit is configured for a Unit Alarm, a Low O
2
, and a High AC Impedance.
Calibration
recommended
.
The unit is configured for a calibration handshake with a Rosemount IMPS 4000 or SPS 4001B.
Calibration recommended
will initiate the calibration cycle.
9
The unit is configured for a calibration handshake.
Calibration recommended
will not
intiate the calibration cycle with the Rosemount IMPS 4000 or SPS 4001B.
(1)
The default condition for a Rosemount
™
Hazardous Area Oxymitter 4000 without a Rosemount IMPS 4000 or SPS
4001B.
(2)
The default condition for a Rosemount Hazardous Area Oxymitter 4000 with a Rosemount IMPS 4000 or SPS 4001B.
Note
The
Calibration recommended
alarm was discontinued in 2014. It is still available in
the Rosemount 6888 product.
The Unit Alarm configuration available for modes 1, 3, 5, and 7 refers to the diagnostic
alarm faults in .
HART
®
/AMS
Reference Manual
October 2019
00809-0100-4340
108
Emerson.com/Rosemount
Summary of Contents for Rosemount Oxymitter 4000
Page 4: ...4 ...
Page 8: ...Contents Reference Manual October 2019 00809 0100 4340 viii Emerson com Rosemount ...
Page 110: ...HART AMS Reference Manual October 2019 00809 0100 4340 110 Emerson com Rosemount ...
Page 114: ...HART AMS Reference Manual October 2019 00809 0100 4340 114 Emerson com Rosemount ...
Page 184: ...Optional accessories Reference Manual October 2019 00809 0100 4340 184 Emerson com Rosemount ...