7. Plug the black four-wire connector into the black socket on the microprocessor
card.
8. Tighten three screws (D) securing the electronics assembly into the termination
housing.
9. In the left side of the termination housing, place the new termination designation
over the labels on the existing terminal block.
After placing the new labels, the terminal block should appear as shown in
Figure A-2: Terminal Block and Wiring
A. Terminal block
B. AC line voltage port
C. Ground lugs
D. Signal port
E. Left side of transmitter
F. 4-20 mA signal
G. Logic I/O or calibration handshake
H. Line voltage (90 to 250 Vac)
I. AC terminal cover
You can reuse the existing wires from the transmitter to the electronics. However,
the wires will be carrying new signals as noted by the new labels.
10. Remove the 4-20 mA wires from the old electronics and re-terminate them to the
wires carrying the 4-20 mA signal to the control room.
11. Convert the wires carrying the heater to power to carry AC power (80-250 Vac,
50/60 Hz) for the transmitter.
The re-termination may be inside the old electronics housing, which will function as
a simple junction box. Alternatively, you can remove the old electronics housing
and replace it with a smaller junction box.
Upgrade Rosemount
™
Oxymitter DR to full Oxymitter
Reference Manual
October 2019
00809-0100-4340
178
Emerson.com/Rosemount
Summary of Contents for Rosemount Oxymitter 4000
Page 4: ...4 ...
Page 8: ...Contents Reference Manual October 2019 00809 0100 4340 viii Emerson com Rosemount ...
Page 110: ...HART AMS Reference Manual October 2019 00809 0100 4340 110 Emerson com Rosemount ...
Page 114: ...HART AMS Reference Manual October 2019 00809 0100 4340 114 Emerson com Rosemount ...
Page 184: ...Optional accessories Reference Manual October 2019 00809 0100 4340 184 Emerson com Rosemount ...