C6.1.6/0117-1017/E
69
Pump-down with temperature sensor in case temperature (not available on ZXDE units)
– System restart is required!
Parameter
Parameter description
Factory setting
Required setting
A19
Probe 7 configuration
nu = Not used
tnt = Thermostat temperature
C05
Compressor regulation probe selection
SuP = Suction pressure probe
CSt = Case temperature
G01
Case temperature probe selection
nu = Not used
tnt = Thermostat temperature
G56
Use the liquid line solenoid
No
Yes
S07
Relay output 4
nu = Not used
LLS = Liquid line solenoid
C01
Compressor cut-in pressure setpoint
4 bar rel
Adjust to application requirements
C02
Compressor cut-out pressure setpoint
2 bar rel
Adjust to application requirements
G02
Cut-out temperature
+2°C
Adjust to application requirements
G03
Positive differential defines upper cut-in temperature
1K
Adjust to application requirements
Defrost with time intervals
– System restart is required!
Parameter
Parameter description
Factory setting
Required setting
A19
Probe 7 configuration
nu = Not used
EPt = Evaporator temperature
G12
Defrost probe selection
nu = Not used
EPt = Evaporator temperature
G23
Defrost interval mode
nu = Not used
In = By time (G18)
S05
Relay output 2
nu = Not used
dEF = Defrost
G18
Interval between defrost cycles
4 min
Adjust to application requirements
G19
Maximum duration of defrost
20 min
Adjust to application requirements
G21
Defrost termination temperature
10
Adjust to application requirements
G26
Drip time
1 min
Adjust to application requirements