2.6 Application range
2.6.1 Qualified refrigerants and oils
Qualified
refrigerants
R404A, R407A, R407F, R507, R448A, R449A
R134a*, R450A*, R513A* (* = Not for ZXLE)
Qualified
servicing
oils
Emkarate RL 32 3MAF
Mobil EAL Arctic 22CC
Oil charge
in litres
ZXME020E
ZXME025E
ZXME030E
ZXLE020E
ZXLE025E
ZXLE030E
ZXDE030E
ZXDE040E
ZXLE040E
ZXLE050E
ZXDE050E
ZXDE060E
ZXDE075E
ZXME040E
ZXME050E
ZXME060E
ZXME075E
ZXLE060E
ZXLE075E
1
1.1
1.24
1.75
1.77
1.85
2.3
Table 1: Qualified refrigerants and oils
WARNING
Use of R450A and R513A refrigerants! Risk of compressor damage!
Migration of R450A or R513A into the compressor crankcase could cause low
oil viscosity, which could lead to compressor damage. When using R450A or
R513A it is critical to meet the following requirements:
▪
maintain adequate superheat settings with a minimum superheat of 8-10K;
▪
no liquid refrigerant migration into the compressor at any time, especially
during standstill, during or after defrost, or after reverse mode for example
in heat pumps;
▪
pump-down is recommended (not for Digital units);
▪
the use of a crankcase heater is mandatory;
▪
retrofit to R450A and R513A is only allowed for compressors which are
approved for these refrigerants.
Contact your local Application Engineering representative for any further
information.
NOTE: ZXDE & ZXLE units are equipped with an oil separator. This separator is pre-charged
with 0.5 liter of oil.
2.6.2 Application limits
For application envelopes, please refer to the compressor application envelopes which can be found
in Copeland
™ brand products Select software, available at
ZX condensing units can be used with an ambient temperature from -15°C to 45°C. For lower ambient
temperatures please contact your local Application Engineering representative.
2.7 Bill of material history
BOM Family
Introduction
date
Controller concept
Oil
separator
Suction
accumulator
302
ZXME
08/2008
Electronic main board
No
No
452
ZXLE
07/2010
Electronic main board
Yes
Yes
ZXDE
EC2-552 (Emerson - Alco)
Yes
No
303
ZXME
03/2013
Electronic main board
No
No
453
ZXLE
03/2013
Electronic main board
Yes
Yes
ZXDE
XC645 (Emerson - Dixell)
Yes
No
304
ZXME
01/2015
XCM25D (Emerson - Dixell)
No
No
454
ZXLE
01/2015
XCM25D (Emerson - Dixell)
Yes
Yes
ZXDE
Yes
No
Table 2: BOM history
NOTE: These guidelines are of application only for BOM 304 and 454. For previous
generations (BOM 302/452 & BOM 303/453) the dedicated guidelines can be downloaded from