C6.1.6/0117-1017/E
55
Code Description
Range
Factory setting
ZXDE ZXME ZXLE
G01
Case temperature probe selection
NU (0-NU)
Mid-coil temperature (1-MCT)
Discharge line temperature (2-DLT)
Ambient temperature (3-AMT)
Thermostat temperature (4-TMT)
Evaporator temperature (5-EPT)
Vapour inlet temp (6-UIT)
Vapour outlet temp (7-UOT)
Liquid temp (8-LLT)
Suction line temperature (9-SLT)
Coil temperature (10-COT)
Not used
L2
L2
L2
G02
Case temperature setpoint
CLS to CUS
2
L2
L2
L2
G03
Case temperature differential
0.1°C to 25.5°C
1
L2
L2
L2
G04
Case temperature low range
-40°C to CUS
-10
L2
L2
L2
G05
Case temperature high range
CLS to 110°C
15
L2
L2
L2
G06
Case probe failure limp along on time
0 to 255 min
2
L2
L2
L2
G07
Case probe failure limp along off time
0 to 255 min
1
L2
L2
L2
G08
Compressor and fan status when open door
>> no = normal operation; Fn = Fans off;
cP = Compressor off; Fc = Compr. & fans off
no (0-NO)
Fn (1-FAN)
cP (2-CPR)
Fc (3-F-C)
NO
L2
L2
L2
G09
Regulation with open door
No (0-NO) - Yes (1-YES)
YES
L2
L2
L2
G10
Liquid/vapour injection switch based on SH
activation
No (0-NO) - Yes (1-YES)
YES
L2
L2
L2
G11
Maximum pump-down time
0 to 255 min
3
L2
L2
L2
G12
Defrost probe selection
nu (0-NU)
Mid-coil temperature (1-MCT)
Discharge Line temperature (2-DLT)
Ambient temperature (3-AMT)
Thermostat temperature (4-TMT)
Evaporator temperature (5-EPT)
Vapour inlet temp (6-UIT)
Vapour outlet temp (7-UOT)
Liquid temp (8-LLT)
Suction line temperature (9-SLT)
Coil temperature (10-COT)
Not used
L2
L2
L2
G13
Defrost in probe selection
Not used
L2
L2
L2
G14
Defrost out probe selection
Not used
L2
L2
L2
G15
Threshold percentage to enable intelligent
defrost
0 to 100
40
L2
L2
L2