C6.1.6/0117-1017/E
58
Code Description
Range
Factory setting
ZXDE ZXME ZXLE
H03
Voltage sensing 1
no; yes
NO
L2
L2
L2
H04
Voltage sensing 2
no; yes
NO
L2
L2
L2
H05
Voltage sensing 3
no; yes
NO
L2
L2
L2
H06
Voltage and current protection enabled
no; yes
YES
L2
L2
L2
H07
Maximum continuous current limit
3PE = 0: 0.0 to 70.0 A
3PE = 1: 0.0 to 35.0 A
Unit dependent
L2
L2
L2
H08
Voltage/current sensing trip minimum off time
0 to 255 min
5
L2
L2
L2
H09
Adjustable current limit before trip
0.0 to MCC Ampere
9.5
L2
L2
L2
H10
Ignore current sensing duration at start-up
duration
0 to 255 sec
3
L2
L2
L2
H11
Number of over current trips before lockout
0 to 15
5
L2
L2
L2
H12
Number of loss of phase trips before lockout
0 to 15
5
L2
L2
L2
H13
Minimum voltage to trip compressor
0 to 400V
360
N.V.
N.V.
N.V.
H14
Maximum voltage to trip compressor
0 to 800V
480
N.V.
N.V.
N.V.
H15
Over or under voltage minimum time
0 to 255 sec
60
L2
L2
L2
H16
Compressor minimum off time because of
voltage error
0 to 255 min
3
L2
L2
L2
H17
Number of compressor trips before lockout
because of voltage
0 to 15
5
L2
L2
L2
H18
Adjustable under average voltage percentage
0 to 100%
90
L2
L2
L2
H19
Generate warning or shut down compressor
when phase imbalance
0: Generate warning (0-ARN)
1: Unit off(1-Off)
Unit off
L2
L2
L2
H20
Missing current duration before warning
0 to 255 sec
10
L2
L2
L2
H21
Minimum high side superheat
-40 to 110°C
10
L2
L2
L2
H22
Amount of time allowed in an interval to check
for floodback
0 to H23 min
30
L2
L2
L2
H23
Interval to check for floodback
H22 to 120 min
45
N.V.
N.V.
L2
H24
Duration of checking anti-floodback alarm
reset condition
1 to 255 min
20
N.V.
N.V.
L2
H25
Three phase enable
no; yes
YES
L2
L2
L2
I01
Ambient temperature threshold to off
crankcase heater
-40°C to 180°C
10
L2
L2
L2
I02
Compressor minimum off time before turning
on the crankcase heater
0 to 255 min
5
L2
L2
L2