16
C6.1.6/0117-1017/E
Parameter
Description
Factory settings /
Range
Recommended settings / Comments
A19
Probe 7
configuration
0 = Not used =
nu
Evaporator temp (NTC10K) = 5 =
EPt
G12
Defrost probe
selection
0 = Not used =
nu
5 = Evaporator temperature sensor =
EPt
G17*
Defrost type
0 = Electrical =
EL
0 = Electrical =
EL
; 1 = Hot gas defrost
(not available on ZX units) =
in
;
2 = Natural defrost (pulse defrost) =
PLS
G18
Interval between
defrost cycles
4 hours
0 to 120 hours range; adjust to individual
requirements
G19
Maximum duration
of defrost
20 minutes
0 to 255 minutes; adjust to individual
requirements
G20
Duration of pulse
defrost
15 minutes
0 to G19
G21
Defrost
termination
temperature
10°C
-40°C to 110°C
G22
Defrost delay time
15 minutes
0 to 255 minutes
G23**
Defrost interval
mode
0 = Not used =
nu
0 =
nu
= Not used; 1 =
in
= Interval;
2 =
rtC
= Real time clock
G24***
Display during
defrost
DEFROST "
dEF
"
0 =
dEF
= Defrost;
1 =
Set
= Case temperature setpoint;
2 =
it
= Case temperature value;
3 =
rt
= Standard operation
G25
Maximum display
delay after defrost
0 minute
0 to 255 minutes
G26
Drip time
1 minute
0 to 120 minutes
G27
Defrost at power-
on
0 =
NO
Avoids defrost after initial power up. If
"YES", the controller will decide on defrost
related parameters if a defrost sequence is
required after initial start-up
G28
Workday defrost
start 1
00:00
00:00
– 23:50 or
nu
= Not used
G29
Workday defrost
start 2
04:00
00:00
– 23:50 or
nu
= Not used
G30
Workday defrost
start 3
08:00
00:00
– 23:50 or
nu
= Not used
G31
Workday defrost
start 4
12:00
00:00
– 23:50 or
nu
= Not used
G32
Workday defrost
start 5
16:00
00:00
– 23:50 or
nu
= Not used
G33
Workday defrost
start 6
20:00
00:00
– 23:50 or
nu
= Not used
G34
Holiday defrost
start 1
00:00
00:00
– 23:50 or
nu
= Not used
G35
Holiday defrost
start 2
04:00
00:00
– 23:50 or
nu
= Not used
G36
Holiday defrost
start 3
08:00
00:00
– 23:50 or
nu
= Not used
G37
Holiday defrost
start 4
12:00
00:00
– 23:50 or
nu
= Not used
G38
Holiday defrost
start 5
16:00
00:00
– 23:50 or
nu
= Not used
G39
Holiday defrost
start 6
20:00
00:00
– 23:50 or
nu
= Not used