C6.1.6/0117-1017/E
71
Evaporator fan
– System restart is required!
Parameter
Parameter description
Factory setting
Required setting
G42
Fans operating mode
cn
cn = Switch on and off with the compressor, stop
during defrost
On = Always on, stop during defrost
cy = Switch on and off with the compressor, run
during defrost
Oy = Always on, run during defrost
S05
Relay output 2
nu = Not used
EPF = Evaporator fan
G45
Fan on time
1 min
Adjust to application requirements
G46
Fan off time
1 min
Adjust to application requirements
G55
Fan delay after defrost
1 min
Adjust to application requirements
System EXV
– System restart is required!
Parameter
Parameter description
Factory setting
Required setting
A19
Probe 7 configuration
nu = Not used
SLt = Suction line temp
L02
Set of superheating
5
7
S11
EXV configuration
uin or Lin
SHt = System superheat
Door switch
– System restart is required!
Parameter
Parameter description
Factory setting
Required setting
G08
Compressor and fan status with open door
Fn
nO = Normal operation
Fn = Stop fan
cP = Compressor off
Fc = Compressor and fans off
R07
Digital input 3 configuration
nu = Not used
dOr = Door
G53
Maximum time with open door before alarm goes off
3 min
Adjust to application requirements
R08
Digital input 3 polarity
CL = Closed
Adjust to application requirements
Table 34: Additional features for customization