C6.1.6/0117-1017/E
31
3.2 Electrical connection
3.2.1 Power supply connections
The electrical connection of the condensing unit to the power supply must be made by qualified
technicians according to the valid electrical directives, for instance DIN EN 60204-1. Also the voltage
drop and temperatures on line must be considered for cable selection.
Copeland EazyCool ZX units are designed for a 380-420V / 3Ph / 50 Hz power supply for TFD and
220-240V / 1Ph / 50 Hz power supply for PFJ. A voltage tolerance of ± 10% is acceptable.
The circuit breaker must be switched off before opening the front door.
WARNING
Electrical shock hazard! Serious personal injuries!
There are unused fast-
on pins (
C1
&
DO2
) on the XCM25D which could be under voltage. They are
covered by insulated fast-on flags in the factory. Handle carefully when
removing insulating flags during service on site.
3.2.2 Maximum operating currents for cable selection
Unit model
Locked rotor
Rated current A
ZXME Medium temperature units, single phase PFJ
ZXME020E-PFJ
58.0
13.3
ZXME025E-PFJ
61.0
12.9
ZXME030E-PFJ
82.0
16.9
ZXME040E-PFJ
114.0
24.0
ZXME Medium temperature units, three phase TFD
ZXME020E-TFD
26.0
5.4
ZXME030E-TFD
40.0
7.7
ZXME040E-TFD
49.3
10.8
ZXME050E-TFD
65.5
13.8
ZXME060E-TFD
74.0
14.1
ZXME075E-TFD
101.0
15.0
ZXDE Medium temperature Digital units, three phase TFD
ZXDE030E-TFD
40.0
7.2
ZXDE040E-TFD
48.0
8.9
ZXDE050E-TFD
64.0
12.3
ZXDE060E-TFD
74.0
12.4
ZXDE075E-TFD
100.0
15.0
ZXLE Low temperature units, single phase PFJ
ZXLE020E-PFJ
56.6
14.1
ZXLE025E-PFJ
73.7
16.1
ZXLE030E-PFJ
82.3
18.3
ZXLE Low temperature units, three phase TFD
ZXLE020E-TFD
39.2
6.2
ZXLE030E-TFD
35.7
7.2
ZXLE040E-TFD
51.5
9.7
ZXLE050E-TFD
51.5
12.9
ZXLE060E-TFD
74.0
14.7
ZXLE075E-TFD
101.0
15.6
Table 27: Maximum operating currents for cable selection
3.2.3 Electrical wiring
Before commissioning, ensure that the neutral "N" and ground protection "PE" wires are connected
to the main switch.
S
afet
y
inst
ru
ctio
n
s
P
ro
d
u
ct
d
es
cr
ipt
ion
Inst
all
atio
n
S
tar
ting
up
&
o
p
er
atio
n
Ma
int
enan
c
e &
repai
r
Cer
tif
ica
tion
&
a
p
p
ro
va
l
Dismant
ling
&
d
ispo
sa
l