C6.1.6/0117-1017/E
56
Code Description
Range
Factory setting
ZXDE ZXME ZXLE
G16
Duration to calculate the average difference
between the diP and doP
0 to 100 min
5
L2
L2
L2
G17
Defrost type
EL (0-EL)
in (1-IN)
Pulse (2-PLS)
EL
L2
L2
L2
G18
Interval between defrost cycles
0 to 120 h
4
L2
L2
L2
G19
Maximum length for defrost
0 to 255 min
20
L2
L2
L2
G20
Duration of pulse defrost
0 to G19
15
L2
L2
L2
G21
Defrost termination temperature
-40°C to 110°C
10
L2
L2
L2
G22
Defrost delay time
0 to 255 min
0
L2
L2
L2
G23
Defrost interval mode
nu (0-NU)
in (1-IN)
rtC (2-rtC)
Intelligent (3-INT)
Not used
L2
L2
L2
G24
Display during defrost
dEF = Defrost;
Set = Setpoint case temp;
it = Case temp;
rt = Display in standard operation
dEF (0-DEF)
Set (1-SET)
it (2-IT)
rt (3-RT)
dEF
L2
L2
L2
G25
Maximum display delay after defrost
0 to 255 min
0
L2
L2
L2
G26
Drip time
0 to 120 min
1
L2
L2
L2
G27
Defrost at power-on
No (0-NO) - Yes (1-YES)
NO
L2
L2
L2
G28
Workday defrost start 1
00:00
– 23:50; nu
0:00
L2
L2
L2
G29
Workday defrost start 2
00:00
– 23:50; nu
4:00
L2
L2
L2
G30
Workday defrost start 3
00:00
– 23:50; nu
8:00
L2
L2
L2
G31
Workday defrost start 4
00:00
– 23:50; nu
12:00
L2
L2
L2
G32
Workday defrost start 5
00:00
– 23:50; nu
16:00
L2
L2
L2
G33
Workday defrost start 6
00:00
– 23:50; nu
20:00
L2
L2
L2
G34
Holiday defrost start 1
00:00
– 23:50; nu
0:00
L2
L2
L2
G35
Holiday defrost start 2
00:00
– 23:50; nu
4:00
L2
L2
L2
G36
Holiday defrost start 3
00:00
– 23:50; nu
8:00
L2
L2
L2
G37
Holiday defrost start 4
00:00
– 23:50; nu
12:00
L2
L2
L2
G38
Holiday defrost start 5
00:00
– 23:50; nu
16:00
L2
L2
L2