C6.1.6/0117-1017/E
59
Code Description
Range
Factory setting
ZXDE ZXME ZXLE
L01
Steps for initial regulation
SH2 to SH1 steps
15
L2
N.V.
L2
L02
Superheating setpoint
0.0°C to 25.5°C
5
L2
N.V.
L2
L03
Threshold of low superheating
0.0 to SH18°C
1
L2
N.V.
L2
L04
Threshold of high superheating
SH17 to 80.0°C
15
L2
N.V.
L2
L05
Extra % of valve close in case of low
superheating
0 to 100%
0
L2
N.V.
N.V.
L06
Delay high superheating
0 to 255 sec
30
L2
N.V.
N.V.
L07
Delay low superheating
0 to 255 sec
30
L2
N.V.
N.V.
L08
Threshold of MOP
SH23 to 60.0°C
35
L2
N.V.
N.V.
L09
Threshold of LOP
-50°C to SH22°C
-20
L2
N.V.
N.V.
L10
Activation delay MOP
0 to 255 sec
1
L2
N.V.
N.V.
L11
Activation delay LOP
0 to 255 sec
1
L2
N.V.
N.V.
L12
Steps close/open in case of MOP/LOP
0 to SH1 steps
20
L2
N.V.
N.V.
M01
Max step valve
SH2 to 800 steps
250
L2
L2
L2
M02
Min step valve
0 to SH1 steps
0
L2
L2
L2
M03
Extra steps of valve close
0 to 100 steps
20
L2
L2
L2
M04
Relax steps
0 to 100 steps
0
L2
L2
L2
M05
Step rate
10 to 100 steps
35
L2
L2
L2
M06
Regulation of the valve 0: automatic, 1:manual
Automatic (0-AUT)
Manual (1-MAN)
Automatic
L2
L2
L2
M07
Steps if manual regulation
SH2 to SH1 steps
15
L2
L2
L2
M08
Proportional band (if 0 the regulation is auto
adaptive)
0 to 50°C
0
L2
L2
L2
M09
Integral time
0 to 255 sec
20
L2
L2
L2
M10
Derivative
0 to 255 sec
0
L2
L2
L2
M11
Dead band
0 to10°C
1
L2
L2
L2
M12
Min % of the valve
0 to SH15
0
L2
L2
L2
M13
Max % of the valve
SH14 to 100
100
L2
L2
L2
M14
Filter on the pressure
1 to 255 sec
1
L2
L2
L2
M15
Interval of updating valve
1 to 255 sec
20
L2
L2
L2
M16
Filter on the temperature [1-100] sec
1 to 255 sec
1
L2
L2
L2