C6.1.6/0117-1017/E
50
Code Description
Range
Factory setting
ZXDE ZXME ZXLE
D31
DLT temperature threshold to trip during cold
start
-40 to 180°C
60
N.V.
N.V.
N.V.
D32
Suction pressure threshold to trip during cold
start
-1.5 to 99.9 bar
0.5
N.V.
N.V.
N.V.
D33
Allowed number of cycle of DLT temperature
trips during cold start
1 to 15
4
N.V.
N.V.
N.V.
D34
Allowed number of cycles of low pressure trips
during cold start
1 to 15
4
N.V.
N.V.
N.V.
D35
Compressor stop time during cold start
1 to 999 sec
180
N.V.
N.V.
N.V.
E01
Condenser fan motor modulation type
Not used (0-NU)
Fan cycling (1-CYC)
Modulated fan (2-MOD)
Modulated fan
L2
L2
L2
E02
Low setpoint for condenser fan map 1 (for
R404A, R507)
-40°C to HT1
10
N.V.
N.V.
N.V.
E03
Lower suction pressure point for condenser
fan map 1 (for R404A, R507)
-1.5 bar to HP1; -21 PSI to HP1
3.3
N.V.
N.V.
N.V.
E04
High setpoint for condenser fan map 1 (for
R404)
LT1 to 110°C
30
N.V.
N.V.
N.V.
E05
High suction pressure point for condenser fan
map 1 (for R404A, R507)
LP1 to 99.9 bar; LP1 to 999 PSI
7.2
N.V.
N.V.
N.V.
E06
Low setpoint for condenser fan map 2 (for
R134)
-40°C to HT2
25
N.V.
N.V.
N.V.
E07
Lower suction pressure point for condenser
fan map 2 (for R404)
-1.5 bar to HP2; -21 PSI to HP2
2.5
N.V.
N.V.
N.V.
E08
High setpoint for condenser fan map 2 (for
R134)
LT2 to 110°C
40
N.V.
N.V.
N.V.
E09
High suction pressure point for condenser fan
map 2 (for R404)
LP2 to 99.9 bar; LP2 to 999 PSI
3.9
N.V.
N.V.
N.V.
E10
Low setpoint for condenser fan map 3 (for
R22)
-40°C to HT3
20
N.V.
N.V.
N.V.
E11
Low suction pressure point for condenser fan
map 3 (for R22)
-1.5 bar to HP3; -21PSI to HP3
5.2
N.V.
N.V.
N.V.
E12
High setpoint for condenser fan map 3 (for
R22)
LT3 to 110°C
30
N.V.
N.V.
N.V.
E13
High suction pressure point for condenser fan
map 3 (for R22)
LP3 to 99.9 bar; LP3 to 999 PSI
6.4
N.V.
N.V.
N.V.
E14
Low setpoint for condenser fan map 4 (for
R407C)
-40°C to HT4
10
N.V.
N.V.
N.V.