C6.1.6/0117-1017/E
27
NOTE: The "Err" message appears in case of a failed programming operation. In this case
push the key again if you want to restart the upload or remove the "Hot Key" to abort the
operation.
2.15.5 How to program a controller using an Emerson "Hot Key" (download)
▪
Turn the controller off.
▪
Insert a pre-programmed "Hot Key" into the 5-pin receptacle and turn the controller on.
▪
The parameter list of the hot key will be automatically downloaded into the controller memory.
The "
doL
" message will blink followed a by a flashing "
End
" label.
▪
After 10 seconds the controller will restart working with the new parameters.
▪
Remove the "Hot Key".
NOTE: The message "Err" is displayed in case of a failed programming operation. In this case
turn the unit off, then on again if you want to restart the download, or remove the "Hot Key"
to abort the operation.
2.16 Troubleshooting
– Alarm history
The controller records the total number of alarm activations (max 50) in the alarm menu (see
Appendix 6
).
Action
Key or display
Notes
Enter menu
Push and release the
ALR
key.
Waiting for action
SEC
The menu to change the section will be entered. The
alarm list section is active.
Enter section list
Press
SET
to confirm. The following list will be
available to select the proper network function.
Select active alarm
code from list
or
Scroll the list of active alarms by alarm number (letter
+ number, A01-A50).
Press
to see the alarm name or code.
Press
to see the next active alarm.
Select the alarm to
see the detailed rtC
information
Enter the sub menu with alarm time details.
Select detailed
information from
active alarm list
or
With the rtC activated:
The
Hur
(hour) parameter is displayed.
Press
to see the alarm hour.
Press
:
Min
is displayed.
Press
to see the alarm minute.
Press
:
dAy
is displayed.
Press
to see the alarm day.
Press
:
MOn
is displayed.
Press
to see the alarm month.
Press
:
YEA
is displayed.
Press
to see the alarm year.
Note: The clock info indicates the START time of the
alarm.
Without the rtC activated:
The
COn
(hours) parameter is displayed.
Press
to see the compressor working hours.
To exit: press
or wait for 15 seconds without
pressing any key.
Exit menu
Press
simultaneously or wait for about 10
seconds without pressing any key.
Table 25: How to check the alarm list
S
afet
y
inst
ru
ctio
n
s
P
ro
d
u
ct
d
es
cr
ipt
ion
Inst
all
atio
n
S
tar
ting
up
&
o
p
er
atio
n
Ma
int
enan
c
e &
repai
r
Cer
tif
ica
tion
&
a
p
p
ro
va
l
Dismant
ling
&
d
ispo
sa
l