C6.1.6/0117-1017/E
44
Appendix 4: Parameter list level 1 (Pr1)
Legend
L1 = Parameter in Level 1 (without password)
L2 = Parameter in Level 2 (with password = 3 2 1)
N.V. = Parameter not accessible
NOTE: When changing parameters C01 (Cin), C02 (CoU) and C05 (CPb) a reset of the controller (interruption of power supply) is required.
Parameter
Description
Range
ZXDE
ZXME
ZXLE
C01
Compressor cut-in pressure setpoint
CoU to US; C02 to C04
N.V.
L1
L1
C02
Compressor cut-out pressure setpoint
LS to Cin; C03 to C01
L2
L1
L1
C07
Refrigerant selection for regulation
R404A (0-404) - R507 (1-507)
R134a (2-134) - R22 (3-R22)
R407C (4-07C) - R407A (5-07A)
R407F (6-07F) - R448A (7-48A)
R449A (8-49A)
L1
L1
L1
C16
Digital compressor setpoint
LS to US; C03 to C04
L1
N.V.
N.V.
C17
Proportional band for compressor regulation
0.1 to 9.9 bar; 0.1 to 99.9 PSI;
1 to 999 KPA; 0.1°C to 25.5°C
L1
N.V.
N.V.
C21
Cycle time for digital compressor
10 to 40 sec
L1
N.V.
N.V.
C24
Minimum capacity for digital compressor
0 to PMA; 0 to C25
L1
N.V.
N.V.
C25
Maximum capacity for digital compressor
PMi to 100; C24 to 100
L1
N.V.
N.V.
D29
Low pressure alarm value (from serial number
16EZ08855M onwards)
0 to 15 bar
L1
L1
L1
E39
Condenser temperature setpoint when fan
setpoint modulation is disabled
-40°C to 110°C
L1
L1
L1
E46
Regulation band of variable fan
0.1°C to 25.5°C
L1
L1
L1
N01
Current minute
0 to 59
L1
L1
L1
N02
Current hour
0 to 23
L1
L1
L1
N03
Date of month
1 to 31
L1
L1
L1
N04
Month
1 to 12
L1
L1
L1
N05
Year
0 to 99
L1
L1
L1
T18
Access to Pr2 level
[0÷999]
L1
L1
L1
Table 31: Parameters level 1