C6.1.6/0117-1017/E
47
Code Description
Range
Factory setting
ZXDE ZXME ZXLE
B05
Coefficient for probe reading filter (0 =
max,100 = disable)
0 to 100, mEd (101)
50
N.V.
N.V.
N.V.
C01
Compressor cut-in pressure setpoint
CoU to US
4
N.V.
L1
L1
C02
Compressor cut-out pressure setpoint
LS to Cin
2
L2
L1
L1
C03
Minimum setpoint for suction
pressure/temperature
P1i to US; -50.0°C to US
0.6
L2
L2
L2
C04
Maximum setpoint for suction
pressure/temperature
LS to P1E; LS to 60.0°C
7.2
L2
L2
L2
C05
Compressor regulation probe selection
NU (0-NU)
Suction pressure probe (1-SUP)
Case temperature (2-CST)
Suction pressure switch (3-dIS)
Suction pressure
probe
L2
L2
L2
C06
EXV closing time before compressor off
0 to 999 sec
0
L2
L2
L2
C07
Refrigerant selection for regulation
R404A (0-404) - R507 (1-507)
R134a (2-134) - R22 (3-R22)
R407C (4-07C) - R407A (5-07A)
R407F (6-07F) - R448A (7-48A)
R449A (8-49A)
R404A
L1
L1
L1
C08
Setpoint offset
NU (0-NU)
Small offset (1-SOF)
Medium offset (2-MOF)
Large offset (3-LOF)
LAO (4-FOF)
Not used
L2
L2
L2
C09
Ambient temperature operation setpoint
-40°C to 110°C
-20
L2
L2
L2
C10
Pressure/Temperature operation for ambient
differential
0.0 to 9.9 bar; 0.0 PSI to 99.9 PSI
0.0°C to 25.5°C
1
L2
L2
L2
C11
Ambient temperature recover differential
0.1°C to 25.5°C
5
L2
L2
L2
C12
Ambient temperature threshold for low
ambient operation
-40°C to 110°C
-10
L2
L2
L2
C13
Temperature/Pressure to end low ambient
timer and resume normal operation
-40°C to 110°C
-1.5 to 99.9 bar; -21 to 999 PSI
10
L2
L2
L2
C14
Compressor minimum on time in low ambient
operation
0 to 255 sec
10
L2
L2
L2
C15
Pressure to end low ambient timer and shut
off the compressor
-1.5 to 99.9 bar; -21.0 to 999 PSI
0.5
L2
L2
L2
C16
Digital compressor setpoint
LS to US
3.3
L1
N.V.
N.V.
C17
Proportional band for compressor regulation
0.1 to 9.9 bar; 0.1 to 99.9 PSI; 0.1°C to 25.5°C
2
L1
N.V.
N.V.