6.1.2 Handling of the spring terminals
All terminal connections of the controller are implemented with mating connectors with spring terminals (push-in
spring connection) and have the following characteristics:
Conductors with cross sections between 0.25 and 2.5 mm² can be used.
All mating connectors are coded and any reverse polarity is therefore ruled out.
A - Installation
For fast installation without tools, direct conductor connection of prefabricated cables (these with 10 mm wire
end sleeves) by simply inserting into the spring terminal is also possible. The orange push button must also be
pressed during insertion to connect flexible wires of 0.25 to 2.5 mm² without wire end sleeve.
B - Disconnetion
The wires are disconnected using a screwdriver (max. 3.5 mm width) via the orange push button at the terminal
connection that has no direct contact to live parts.
Step 1:
Press the orange push button vertically downwards using a screwdriver to detach the connection.
Step 2:
Pull wire upwards.
C - Test
For voltage testing, each terminal connection has openings for probe tips of multimeters that are designed with
protection against direct contact.
NOTICE
Risk of damage!
All mating connectors
must always
be guided vertically and attached / disconnected
without twisting so that the pins on the main board are not bent and damaged.
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Page 244: ...Firmware V3 15 21 04 2021 244 401 ...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Page 372: ...Firmware V3 15 21 04 2021 372 401 ...