5.2.1 Necessary and optional sensors
Depending on the controller type and the operating mode (single-zone operation / two-zone operation), there
are necessary and optional temperature sensors for the case controller. A sensor scan is performed
automatically during
Erstanlauf - Regler auf Werkseinstellungen zurücksetzen
of the controller. The number of
scanned sensors can be checked in the menu (6-1) or with the LDSWin PC software. This allows unconnected
sensors to be removed from the monitoring for sensor fault.
The following list shows the necessary and optional temperate sensors for the regulation.
Controller type
Sensors necessary for regulation
Optional sensors
(advanced functions)
Single-zone operation
UA 111 / UA 141
R2.1
R2.2 R2.3 R2.4 R4.1 R4.2 R4.3 R4.4
UA 121 / UA 131 / UA 131 LS
R1.1 R2.1
R1.2 R1.3 R1.4 R2.3 R4.1 R4.2 R4.3 R4.4
UR 141 NK
R4.1
R1.1 R1.2 R1.3 R2.1 R2.3 R1.4 R4.2 R4.3
R4.4
UR 141 TK
R1.1 R4.1
R1.2 R1.3 R1.4 R2.1 R2.3 R4.2 R4.3 R4.4
UA 111 D
R2.1
R2.2 R2.3 R2.4 R2.5 R4.1 R4.2 R4.3 R4.4
R4.5
UA 131 DD
–
R1.1 R1.2 R1.3 R1.4 R2.1 R2.3 R4.1 R4.2
R4.3 R4.4
Two-zone operation
UA 111 / UA 141
R2.1 R2.3
R2.2 R2.4 R4.1 R4.2 R4.3 R4.4
UA 121 / UA 131 / UA 131 LS
R1.1 R1.3 R2.1 R2.3
R1.2 R1.4 R4.1 R4.2 R4.3 R4.4
UR 141 NK
R4.1 R4.3
R1.1 R1.2 R1.3 R1.4 R2.1 R2.3 R4.2 R4.4
UR 141 TK
R1.1 R1.3 R4.1 R4.3
R1.2 R1.4 R2.1 R2.3 R4.2 R4.4
UA 111 D
Not applicable as controller type does not support
two-zone operation
UA 131 DD
–
R1.1 R1.2 R1.3 R1.4 R2.1 R2.3 R4.1 R4.2
R4.3 R4.4
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Page 244: ...Firmware V3 15 21 04 2021 244 401 ...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Page 372: ...Firmware V3 15 21 04 2021 372 401 ...