![ECKELMANN UA 400 Operating Instruction Download Page 207](http://html.mh-extra.com/html/eckelmann/ua-400/ua-400_operating-instruction_533231207.webp)
Firmware V3.15
21.04.2021
207/401
•
•
•
Menu 2-1-4 Zone 2A Altern.
COOLING 2A POS: XXXXX
Entry
Default
Setpoint R2.3 XXX °C
Supply air temperature setpoint
-10..20
0 °C
Hystersis R2.3 X K
Supply air temperature hysteresis setpoint
1..8
4 K
Setpoint R4.3 XXX °C
Return air temperature setpoint for comparison
-10..20
4 °C
Hystersis R4.3 X K
Return air temperature hysteresis setpoint
1..8
2 K
Menu 2-2 Defrost
DEFROST POS: XXXXX
1 Zone 1
Menu 2-2-1
2 Zone 2
Menu 2-2-2
Only shown when two-zone operation is set (Menu 6-1)
3 Zone 1A Altern.
Menu 2-2-3
Not shown when setpoint toggle is disabled (Menu 3-3)
4 Zone 2A Altern.
Menu 2-2-4
Only shown when two-zone operation is set (Menu 6-1) and setpoint toggle is not
disabled (Menu 3-3)
Menu 2-2-1 Zone 1
DEFROST 1 POS: XXXXX
Entry
Default
Def. End. Tmp. XX °C
Defrost termination temperature setpoint
--, 5..20
8 °C
Wait Time xx m
Waiting time setpoint between cooling and
defrosting
0 .. 15
0 m
Drip Time x m
Waiting time (drain time) setpoint between
defrosting and cooling
0 .. 15
0 m
M/S Degiv.Fct. XXX
Configuration of the defrost via CAN bus function.
For details see chapter
Abtau-Synchronisation über CAN-Bus
OFF, MASTR, SLAVE
OFF
M/S CAN Adr. XXX
Selection of the controller (1..99) participating in
the defrost via CAN bus which is the master.
"--", if this controller is itself master(Parameter
M/
S Degiv.Fct.
. = MASTR)
---, 1..99
–
DS-Function XXX
Configuration of the defrost sequence function
(DS).For details see chapter
OFF, MASTR, SLAVE
OFF
DS-Group XXX
Selection of which group a defrost sequence of
this controller (1..99) belongs to.
---, 1..99
–
DS-Master XXX
Selection of which controller (1..99) participating
in the defrost sequence is the master.
"--", if this controller is itself the master(Parameter
DS-Function
= MASTR)
---, 1..99
–
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Page 244: ...Firmware V3 15 21 04 2021 244 401 ...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Page 372: ...Firmware V3 15 21 04 2021 372 401 ...