Firmware V3.15
21.04.2021
162/401
•
•
•
•
Menu 6-2 - Controller
REGLER POS: XXXXX
1 Type and version
Continue to menu 6-2-1
2 Temperature display
Continue to menu 6-2-2
3 Alarm delay
Continue to menu 6-2-3
4 230 V inputs
Continue to menu 6-2-4
5 Sensor type
Continue to menu 6-2-5
Menu 6-2-1 Type and version
VERSION POS: XXXXX
Input
Default
ReglertypXXXXXXX
Controller type that is set using the DIP switch S3
–
UA111
Software Vers.:XXXX
Software version of the case controller
–
x.yy
Gerät Nr:XXXXXX
Serial number of the case controller
–
Master/Sl. ModeXXX
Synchronised defrost in the master / slave mode
(ON/OFF)
–
Menu 6-2-2 Temperature display
ANZEIGE POS: XXXXX
Input
Default
OffsetXX K
Offset for the display of the temperature
-10..10
0K
AlarmsymbolX
Display of the alarm sysmbol in the temperature
display of the BT30
,
, (Y, N)
N
Menu 6-2-3 Alarm delay
ALARMVERZ. ID: XXXXX
Input
Default
FühlerbruchXX m
Alarm delay for sensor fault
0..30
15 min
Über/Unter TmpXX m
Alarm delay for overtemperature / low
temperature
0..120
60 min
keine AbtauungXX h
Alarm delay for no defrost
--, 2..168
24 h
SelbsthaltungX
NO: Automatic reset of non-transient alarms.
YES: Alarms must be reset manually.
,
, (Y/N)
N
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Page 244: ...Firmware V3 15 21 04 2021 244 401 ...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Page 372: ...Firmware V3 15 21 04 2021 372 401 ...