Firmware V3.15
21.04.2021
115/401
7.6 Terminal assignment of the 0..10 V analogue outputs
Controller
Type
Terminal No.
Analogue output 2
Analogue output 1
All controllers
32
GND
–
31
AO2 (+ 0..10 V)
without function
–
30
–
GND
29
–
AO1 (+ 0..10 V)
without function
Warning - hazardous electrical voltage!
Connecting mains power to the analogue outputs will lead to
the destruction of the controller!
Malfunctions due to interference sources:
All leads running to and from the case controller must be
shielded (cable type: LiYCY)! No shielding is required on sensor leads when installed exclusively
inside the refrigerated display case and when external interference (for example from parallel power
wires) is not to be expected (see operating instruction “Basics and General Safety and Connection
Instructions”). As a general rule, care should be taken to ensure that signal leads and leads carrying a
supply voltage are routed through separate cable channels.