Firmware V3.15
21.04.2021
64/401
5.8 Automatic on/off control
Controller type: UA 141 only
The counter can be switched on and off by a voltage pulse (on-site push button switch, min. 6 sec.) at the 230
V AC counter shutdown digital input. As with manual shutdown, all controlled functions are switched off. The
function of the digital input can be configured via the parameter „
Inv. D3
" (i.e. Inv. D2) in menu 6-2-4.
Additionally, electrical loads on the counter that are not controlled, e.g. lighting, fans and frame heaters, can be
switched on and off through an external relay at the transistor output (terminals 91/92/93).
Switch-on:
Up to 7 control times for automatic restarting of the counter can be set on an internal timer. The same 230 V
input is usable as an external input for setpoint toggling, in which case the on-off function will not be available.
The counter is switched on either by a voltage pulse applied to digital Input 2 or by the control times. The
transistor output (terminals 91/92/93) is set to 24 V / 50 mA.
Switch-off:
As with manual shutdown, all controlled functions are switched off by the voltage pulse applied to digital Input 2
(terminals D21/D22). The transistor output (terminals 91/92/93) is set to 0 V.
Warning - hazardous electrical voltage! Danger of electric shock! BEFORE
connecting and
disconnecting it must be checked that the 230 V AC digital inputs are
off load
! The controller and
connected voltage carrying components remain supplied with power!
Counter shutdown can be activated via digital Input 2 (terminals D21/D22, factory setting. This requires
digital Input 2 to be set as AUTO ACTU. for the switch on/off function to be available.
Parameters of the internal restart time are displayed and can be adjusted when setpoint toggle is set to
"INT" or "---" (see Screen 3-3 in the UA 141 menu structure).
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Page 244: ...Firmware V3 15 21 04 2021 244 401 ...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Page 372: ...Firmware V3 15 21 04 2021 372 401 ...