Firmware V3.15
21.04.2021
168/401
•
Menu 6-7-1 SDS TEV
SDS TEV POS: XXXXX
Input
Default
SDS TEV xx m
Basic participation of the controller in the suction
pressure shift. Note: This is transmitted via a CAN bus
telegram and intervenes in the regulation!
,
, (ON/OFF)
OFF
Inakt.n.Abt xx m
Delay time after completion of the defrost before the
controller actively intervenes in the suction pressure shift
again.
0..40
30 min
Vrz_HystEIN xx m
Delay time for the reduction request with active cooling
and overshoot of the hysteresis.
0..10
2.5 min
ÜTempZ1 ab. xx m
Delay time before expiry of the high temperature zone 1
alarm delay before the reduction is requested
0..15
5 min
ÜTempZ2 ab. xx m
Delay time before expiry of the high temperature zone 2
alarm delay before the reduction is requested
0..15
5 min
TolÜbHystZ1 x K
Tolerance limit above setpoint plus hysteresis in zone 1.
Influences when to switch from Hold to Lower.
0..20
2 K
TolÜbHystZ2 x K
Tolerance limit above setpoint plus hysteresis in zone 2.
Influences when to switch from Hold to Lower.
0..20
2 K
Umsch_Zu_Rü xxx
Switching from supply air to return air and vice versa
during temperature alarm delay time
,
, (ON/OFF)
OFF
Verz Umsch xx m
Switchover of supply/return air: specifies when the
switchover takes place within the high temperature alarm
delay time
0..15
5 min
Add.Istwrte xxx
Creation of additional debug archives in the system
centre / store computer
.
Attention: can force a reorganisation of the actual value
archives in the system centre / store computer! Only use
when required!
,
, (ON/OFF)
OFF
Steig_OberG xxx K
Upper limit of the neutral zone for gradient determination. 0..5
0.3 K
Steig_UntrG xxx K
Lower limit of the neutral zone for gradient determination. 0..5
0.2 K
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Page 244: ...Firmware V3 15 21 04 2021 244 401 ...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Page 372: ...Firmware V3 15 21 04 2021 372 401 ...