Firmware V3.15
21.04.2021
373/401
•
•
•
•
•
•
•
•
Menu 3-2-a Def.Tim.Z2
DEFR.TIMER POS: XXXXX
Entry
Default
Defrost Timer XXX
Setting for how temperature zone 2 should
defrost:
With Z1 Together with zone 1
INT Internally
EXT Externally – the defrost of both
temperature zones is started
simultaneously via the external signal
,
, (ViaZ1,
ViaZ1,EXT,INT)
ViatZ1
Safe Defr Time XXX m
Safe defrost time, i.e. max. allowed duration of
defrosting (internal defrost only)
0..120
60 min
Manual Defrost XXX
Status (ON/OFF) of auxiliary manual defrost *)
,
, (ON/OFF)
OFF
Defr. 1 xxxxx hh:mm
Defrost start time for internal defrost; weekday,
time of day; shown only when parameter
defrost
timer
= INT
,
, (Mo-Su) or numbers
(hh:mm)
Mo-Su
01:00
...
Defr. 14 xxxxx hh:mm
Menu 3-3 Toggle Setpoints
TOGGLE POS: XXXXX
Entry
Default
Status XXX
Setpoint toggle status (OFF/ON) of alternative
set of setpoints (setpoint toggle)
Toggle Setp. XXX
Setpoint toggle via
EXT digital input D21/22
INT internal timer
CAN bus- „--" deactivated
Note: Care should be taken that the
corresponding digital input D21/D22 is set to
SOLLW.UMSCH (menu 6-2-4)
,
, (EXT, INT, CAN, --)
EXT
Alt
ON: DD-DD hh:mm
Start time for toggle to alternative set of
setpoints
Weekday from - to XXXXX, time hh:mm
Only shown when internal setpoint toggle is
activated (Menu 3-3)
,
, (Mo-Su etc.) or numbers
(hh:mm)
Mo-Su
21:00
Alt
OFF: DD-DD hh:mm
End time for toggle to alternative set of setpoints
Weekday from - to XXXXX, time hh:mm
Only shown when internal setpoint toggle is
activated (Menu 3-3
,
, (Mo-Su etc.) or numbers
(hh:mm)
Mo-Su
05:00
Alt
ON: DD-DD hh:mm
Start time for toggle to alternative set of
setpoints
Weekday from - to XXXXX, time hh:mm
Only shown when internal setpoint toggle is
activated (Menu 3-3)
,
, (Mo-Su etc.) or numbers
(hh:mm)
Su
05:00
Alt
OFF: DD-DD hh:mm
End time for toggle to alternative set of setpoints
Weekday from - to XXXXX, time hh:mm
Only shown when internal setpoint toggle is
activated (Menu 3-3
,
, (Mo-Su etc.) or numbers
(hh:mm)
Su
21:00
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Page 244: ...Firmware V3 15 21 04 2021 244 401 ...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Page 372: ...Firmware V3 15 21 04 2021 372 401 ...