Firmware V3.15
21.04.2021
334/401
•
•
•
•
Menu 2-5-1 Mode altern.
Select between values. Checkmark shows current setting.
MODE POS: XXXXX
Entry
Default
fixed run time
Fixed frame heater on time
enthalpy-ctrl rtm
Enthalpy control by ambient air temperature and
humidity
Menu 2-5-2 Setpoint frame heater
SETPOINTS POS: XXXXX
Entry
Default
Mod: xxxxxxxxxxxx
Displays set frame heater mode (Menu 2-5-1)
Fixed on time
Run Time XXX %
Fixed on time, Only shown when mode set to
Fixed On Time (Menu 2-5-1)
--, 0..100
100 %
emerg.run time XXX %
On time in failure of ambient air humidity or
temperature signal (via CAN bus)
Only shown when mode set to Enthalpy Control
(Menu 2-5-1)
--, 0..100
100 %
enthalp. offs. XXX %
Offset to on time with activated enthalpy control
(via CAN bus)
Only shown when mode set to Enthalpy Control
(Menu 2-5-1)
-50..50
0 %
Invert Output xxx
Inversion of the function of the frame heater
output(terminal 91/92)
,
, (ON/OFF)
ON
Menu 2-5-3 Mode altern.
Select between values. Checkmark shows current setting.
MODE ALT POS: XXXXX
Entry
Default
fixed run time
Fixed frame heater on time
enthalpy-ctrl rtm
Enthalpy control by ambient air temperature and
humidity
Menu 2-5-4 Setpoint altern.
SOLLW. UM POS: XXXXX
Entry
Default
Mod: xxxxxxxxxxxx
Displays set frame heater mode (Menu 2-5-3
Fixed on time
Run Time XXX %
Fixed on time, Only shown when mode set to
Fixed On Time (Menu 2-5-3)
--, 0..100
100 %
emerg.run time XXX %
On time in failure of ambient air humidity or
temperature signal (via CAN bus)
Only shown when mode set to Enthalpy Control
(Menu 2-5-3)
--, 0..100
100 %
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Page 244: ...Firmware V3 15 21 04 2021 244 401 ...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Page 372: ...Firmware V3 15 21 04 2021 372 401 ...