Firmware V3.15
21.04.2021
180/401
•
•
•
•
•
Menu 2-4-2 Zone 2
Not used with this controller type
Menu 2-4-3 Zone 1A Altern.
ALARM 1A POS: XXXXX
Entry
Default
High Temp Setp XX °C
High temperature setpoint at which
High
Temperature
alarm is generated
0..30
8 °C
Low Temp Setp. XX K
Low temperature setpoint (difference below
temperature control setpoint) at which
Low
Temperature
alarm is generated
--, 0..6
4 K
Menu 2-5 Frame Heater
FRAME HTR POS: XXXXX
1 Mode altern.
Move to menu 2-5-1
2 Setpoint frm htr
Move to menu 2-5-2
3 Mode altern.
Move to menu 2-5-3
Not shown when setpoint toggle is disabled (Menu 3-3)
4 Setpoint altern.
Move to menu 2-5-4
Not shown when setpoint toggle is disabled (Menu 3-3)
Menu 2-5-1 Mode altern.
Select between values. Checkmark shows current setting.
MODE POS: XXXXX
Entry
Default
fixed run time
Fixed frame heater on time
enthalpy-ctrl rtm
Enthalpy control by ambient air temperature and
humidity
Menu 2-5-2 Setpoint frame heater
SETPOINTS POS: XXXXX
Entry
Default
Mod: xxxxxxxxxxxx
Displays set frame heater mode (Menu 2-5-1)
Fixed on time
Run Time XXX %
Fixed on time, Only shown when mode set to
Fixed On Time (Menu 2-5-1)
--, 0..100
100 %
emerg.run time XXX %
On time in failure of ambient air humidity or
temperature signal (via CAN bus)
Only shown when mode set to Enthalpy Control
(Menu 2-5-1)
--, 0..100
100 %
enthalp. offs. XXX %
Offset to on time with activated enthalpy control
(via CAN bus)
Only shown when mode set to Enthalpy Control
(Menu 2-5-1)
-50..50
0 %
Invert Output xxx
Inversion of the function of the frame heater
output(terminal 91/92)
,
, (ON/OFF)
ON
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Page 244: ...Firmware V3 15 21 04 2021 244 401 ...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Page 372: ...Firmware V3 15 21 04 2021 372 401 ...