Menu 2-2-3 Zone 1A Altern.
DEFROST 1A POS: XXXXX
Entry
Default
Def. End. Tmp. XX °C
Defrost termination temperature setpoint
--, 0..30
5 °C
Wait Time xx m
Waiting time setpoint between cooling and
defrosting
0 .. 15
0 m
Drip Time x m
Waiting time (drain time) setpoint between
defrosting and cooling
0 .. 15
0 m
2.Defrst Level xx °C
Setpoint 2nd defrost stage
--, -20..30
– °C
Menu 2-2-4 Zone 2A Altern.
DEFROST 2A POS: XXXXX
Entry
Default
Def. End. Tmp. XX °C
Defrost termination temperature setpoint
--, 0..30
5 °C
Wait Time xx m
Waiting time setpoint between cooling and
defrosting
0 .. 15
0 m
Drip Time x m
Waiting time (drain time) setpoint between
defrosting and cooling
0 .. 15
0 m
Menu 2-3 Fan
FANS POS: XXXXX
1 Zone 1
Move to menu 2-3-1
2 Zone 2
Move to menu 2-3-2
Only shown when two-zone operation is set (Menu 6-1)
3 Zone 1A Altern.
Move to menu 2-3-3
Not shown when setpoint toggle is disabled (Menu 3-3)
4 Zone 2A Altern.
Move to menu 2-3-4
Only shown when two-zone operation is set (Menu 6-1) and setpoint toggle is not
disabled (Menu 3-3)
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Page 244: ...Firmware V3 15 21 04 2021 244 401 ...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Page 372: ...Firmware V3 15 21 04 2021 372 401 ...