Firmware V3.15
21.04.2021
154/401
•
•
Menu 2-5-3 Mode altern.
Select between values. Checkmark shows current setting.
MODE ALT POS: XXXXX
Entry
Default
fixed run time
Fixed frame heater on time
enthalpy-ctrl rtm
Enthalpy control by ambient air temperature and
humidity
Menu 2-5-4 Setpoint altern.
SOLLW. UM POS: XXXXX
Entry
Default
Mod: xxxxxxxxxxxx
Displays set frame heater mode (Menu 2-5-3)
Fixed on time
Run Time XXX %
Fixed on time, Only shown when mode set to
Fixed On Time (Menu 2-5-3)
--, 0..100
100 %
emerg.run time XXX %
On time in failure of ambient air humidity or
temperature signal (via CAN bus)
Only shown when mode set to Enthalpy Control
(Menu 2-5-3)
--, 0..100
100 %
enthalp. offs. XXX %
Offset to on time with activated enthalpy control
(via CAN bus)
Only shown when mode set to Enthalpy Control
(Menu 2-5-3)
-50..50
0 %