![ECKELMANN UA 400 Operating Instruction Download Page 147](http://html.mh-extra.com/html/eckelmann/ua-400/ua-400_operating-instruction_533231147.webp)
Firmware V3.15
21.04.2021
147/401
•
•
•
•
9.1.3 Menu 2 Setpoints UA 111
SETPOINTS POS: XXXXX
1 Cooling
Move to menu 2-1 Special case: Move to menu 2-1-1 when single-zone operation is
set (Menu 6-1) and setpoint toggle is disabled (Menu 3-3).
2 Defrost
Move to menu 2-2 Special case: Move to menu 2-2-1 when single-zone operation is
set (Menu 6-1) and setpoint toggle is disabled (Menu 3-3).
3
Not used with this controller type
4 Alarm
Move to menu 2-4 Special case: Move to menu 2-4-1 when single-zone operation is
set (Menu 6-1) and setpoint toggle is disabled (Menu 3-3).
5 Frame Heater
Move to menu 2-5
Menu 2-1 Cooling
COOLING POS: XXXXX
1 Zone 1
Menu 2-1-1
2 Zone 2
Menu 2-1-2
Only shown when two-zone operation is set (Menu 6-1)
3 Zone 1A Altern.
Menu 2-1-3
Not shown when setpoint toggle is disabled (Menu 3-3)
4 Zone 2A Altern.
Menu 2-1-4
Only shown when two-zone operation is set (Menu 6-1) and setpoint toggle is not
disabled (Menu 3-3)
Menu 2-1-1 Zone 1
COOLING 1 POS: XXXXX
Entry
Default
Setpoint R2.1 XXX °C
Supply air temperature setpoint
-10..20
-2 °C
Hystersis R2.1 X K
Supply air temperature hysteresis setpoint
1..8
4 K
Setpoint R4.1 XXX °C
Return air temperature setpoint for comparison
-10..25
5 °C
Hystersis R4.1 X K
Return air temperature hysteresis setpoint
1..8
2 K
Menu 2-1-2 Zone 2
COOLING 2 POS: XXXXX
Entry
Default
Setpoint R2.3 XXX °C
Supply air temperature setpoint
-10..20
-2 °C
Hystersis R2.3 X K
Supply air temperature hysteresis setpoint
1..8
4 K
Setpoint R4.3 XXX °C
Return air temperature setpoint for comparison
-10..25
5 °C
Hystersis R4.3 X K
Return air temperature hysteresis setpoint
1..8
2 K
Menu 2-1-3 Zone 1A Altern.
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Page 244: ...Firmware V3 15 21 04 2021 244 401 ...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Page 372: ...Firmware V3 15 21 04 2021 372 401 ...