Firmware V3.15
21.04.2021
367/401
•
•
Menu 2-4-1 Zone 1
ALARM 1 POS: XXXXX
Entry
Default
High Temp Setp XX °C
High temperature setpoint at which
High
Temperature
alarm is generated
-30..30
-12 °C
Low Temp Setp. XX K
Low temperature setpoint (difference below
temperature control setpoint) at which
Low
Temperature
alarm is generated
--, 0..6
2 K
Menu 2-4-2 Zone 2
ALARM 2 POS: XXXXX
Entry
Default
High Temp Setp XX °C
High temperature setpoint at which
High
Temperature
alarm is generated
-30..30
-12 °C
Low Temp Setp. XX K
Low temperature setpoint (difference below
temperature control setpoint) at which
Low
Temperature
alarm is generated
--, 0..6
2 K