Firmware V3.15
21.04.2021
285/401
•
•
Menu 6-6 Em.Powersupply (Emergency Power supply)
EM.POW.SUP POS: XXXXX
Entry
Default
Cool.funct.OFF xxx
Functionality of the cooling switched off during
emergency power supply? (Y/N)
,
, (Y/N)
N
Defr.funct.OFF xxx
Functionality of the defrosting switched off during
emergency power supply? (Y/N)
,
,(Y/N)
N
Fan funct. OFF xxx
Functionality of the fan switched off during
emergency power supply? (Y/N)
,
, (Y/N)
N
Frame fct.OFF xxx
Functionality of the frame heater off during
emergency power supply? (Y/N)
,
,(Y/N)
N
Light fct. OFF xxx
Functionality of the light during emergency power
supply? (Y/N)
,
, (Y/N)
N
Menu 6-7 Enhanced
ENHANCED POS: XXXXX
1 SDS TEV
Move to menu 6-7-1
2 Service Mode
Move to menu 6-7-2