9.3 Controller type UA 121 - menu tree
DIP switch S3
UA 121
1: ON
2: OFF
3: OFF
4: ON/OFF = Master / Slave mode ON/OFF
5..8: OFF
9: ON
Main menu
Submenu
Submenu 2
Menu number
Menu name
0
REFRIGERATION POINT
Actual values
1
ACTUAL VALUES
Temperature sensor
1-1
TEMPERATURE
Cooling Zone 1
1-2
COOLING 1
Defrost Zone 1
1-3
DEFROST 1
–
Alarm
1-5
ALARM
Frame heater
1-6
FRAME HEATER
Cooling Zone 2
1-7
COOLING 2
Defrost Zone 2
1-8
DEFROST 2
Setpoints
2
SETPOINTS
Cooling
2-1
COOLING
Zone 1
2-1-1
COOLING 1
Zone 2
2-1-2
COOLING 2
Zone 1 U Umschalt.
2-1-3
COOLING 1U
Zone 2 U Umschalt.
2-1-4
COOLING 2U
Defrost
2-2
DEFROST
Zone 1
2-2-1
DEFROST 1
Zone 2
2-2-2
DEFROST 2
Zone 1 U Umschalt.
2-2-3
DEFROST 1U
Zone 2 U Umschalt.
2-2-4
DEFROST 2U
–