Firmware V3.15
21.04.2021
336/401
•
•
9.7.4 Menu 3 Clock UR 141 NK
CLOCK POS: XXXXX
1 Current Time
Move to menu 3-1
2 Defrost timer
Move to menu 3-2
3 Toggle Setpoints
Move to menu 3-3
Menu 3-1 Current Time
CLOCK POS: XXXXX
Entry
Default
Date: XX dd.mm.yy
Display and enter current weekday, date
dd.mm.yy
Time: hh.mm
Display and enter current time
hh.mm
Daylight Saving X
Display and enter automatic daylight saving
change (Y/N)
,
,(Y/N)
J
Menu 3-2 Defrost timer
DERF. TIMER POS: XXXXX
Entry
Default
Defrost timer XXX
Defrost initiation via input D11/12 ( EXT) or
internal (INT)
,
, (EXT, INT)
INT
Safe Defr Time XXX m
Safe defrost time for maximum allowed
duration of defrosting (used only for internal
defrosting)
0..180
90 min
Manual Defrost XXX
Status (OFF/ON) for supplementary manual
defrosting *) shown only when parameter
defrost timer = INT
,
, (ON/OFF)
OFF
Def.Tim.Z2
Separate defrost timer for zone 2
Menu 3-2-a
Defr. 1 xxxxx hh:mm
Defrost start time with internal defrosting;
Weekday, time; shown only when parameter
defrost timer = INT
,
, (Mo-Su etc.) or
numbers (hh:mm)
Mo-Su01:00
Defr. 2 xxxxx hh:mm
Defrost start time with internal defrosting;
Weekday, time; shown only when parameter
defrost timer = INT
,
, (Mo-Su etc.) or
numbers (hh:mm)
Mo-Su06:00
Defr. 3 xxxxx hh:mm
Defrost start time with internal defrosting;
Weekday, time; shown only when parameter
defrost timer = INT
,
, (Mo-Su etc.) or
numbers (hh:mm)
Mo-Su13:00
Time is defined by time master (system centre / store computer / operator terminal) when CAN bus is
connected. Any entry made will then be overwritten by the defined value.
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Page 244: ...Firmware V3 15 21 04 2021 244 401 ...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Page 372: ...Firmware V3 15 21 04 2021 372 401 ...