6 Object dictionary for XN-312-GW-CAN gateway
6.3 Error Register
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
83
6.3.2 Object 1003
hex
Error History
Object 1003
hex
is used to log the gateway's last six EMCY frames. These
frames can be read by the CAN master as a history at any time. In other
words, this object holds the gateway's internal faults in a single byte
Table 11:
Description of object 1003
hex
6.3.3 Objekt 1029
hex
Error Behaviour Object/Communication Error (rw)
Object 1029
hex
(error behavior object/communication error (rw)) defines
what the response to a guarding error will be. For more information, please
refer to CiA DS301, sec. 7.5.2.32, Default = Switch to Pre-Operational.
Data type
Sub index 00
hex
Unsigned8
Access
Sub index 00
hex
ro
Default value XN300
Sub index 00
hex
0x0
Error Register
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
generic
Current
Voltage
0
Comm.
0
0
Manu.
Abbreviations
generic
Group fault
Current
Short-circuit on output/
Current fault
Voltage
Voltage fault
Comm.
communication error
(communication fault)
Manu.
manufacturer specific error
Feature
Sub index
Description / Value
Feature
Sub index
Description / Value
Name
Error Register
Object code
VAR
PDO mapping
Yes
Data type
Sub index 00
hex
Unsigned32; number of error entries
Access
Sub index 00
hex
ro
Default value XN300
Sub index 00
hex
no; number of error entries
Data type
Sub index 01
hex
… 0F
hex
Unsigned32; error entries
Summary of Contents for XN-312-GW-CAN
Page 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Page 4: ...II ...
Page 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Page 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Page 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...