7 Product-specific CAN objects XN300 slice modules
7.21 XN-322-4AIO-I
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
277
7.21.11 Module Diagnostic Messages (Object 0x31B0)
Object 0x31B0
contains status information on the module's general operat-
ing status.
Design of the data bytes:
Byte 0:
Sub-Index 1
≦
n
≦
254
Byte 1:
Sub-Index 1
≦
n
≦
254
Feature
Description / Value
EDS
Name
ModuleDiag
[MxSubExt31B0]
ParameterName=ModuleDiag
ObjectType=0x7
DataType=0x0006
AccessType=ro
PDOMapping=1
Count=1
Description
Module Diagnostic Messages
Object Code
ARRAY
Mapping
PDO
Manual
Data type
UNSIGNED16
Sub index
01 … FE
hex
Access
ro
7
6
5
4
3
2
1
0
–
–
–
Data bit
Designation
Description
0
reserved
1
0 = sync OK
1 = no sync
2
0 = OK
1 = FLASH Data CRC Error
3
0 = OK
1 =RAM Data CRC Error
4
0 = OK
1 = Inconsistent FLASH Data
5
0 = OK
1 = Invalid configuration
6 – 7
reserved
7
6
5
4
3
2
1
0
–
–
CLASS
CLASS
CLASS
TYPE
TYPE
TYPE
Data bit
Designation
Description
8 – 15
reserved
Summary of Contents for XN-312-GW-CAN