7 Product-specific CAN objects XN300 slice modules
7.24 XN-322-1DCD-B35
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
319
Design of the data bytes:
7.24.6 Read Period Duration of Sequence Cycle (Object 0x30E4)
Object 0x30E4 can be used to read the duration of the motor control PWM
output sequence.
Feature
Description / Value
EDS
Name
RDSeq1
Object 0x30E0
[MxSubExt30Ex]
ParameterName=RDSeq1
ObjectType=0x7
DataType=0x0006
AccessType=ro
PDOMapping=1
Count=1
RDSeq2
Object 0x30E1
RDSeq3
Object 0x30E2
RDSeq4
Object 0x30E3
Description
Read PWM Sequence Data
Object Code
ARRAY
Mapping
PDO
Manual
Data type
UNSIGNED16
Sub index
01 … FE
hex
Access
ro
1 Byte
Byte 0:
Sub index
1
≦
n
≦
254
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
MSB
Time value / clock frequency
Data bit
Desig-
nation
Description
0 – 7
Time value / clock frequency
8 – 10
Time value / clock frequency
11
0 = relative time counter
1 = absolute time counter
12
0 = OFF
1 = left high ON
13
0 = OFF
1 = right high ON
14
0 = OFF
1 = left low ON
15
0 = OFF
1 = right low ON
Period Time=
RDPeriodDurationSeq
Clock frequency
Summary of Contents for XN-312-GW-CAN