7 Product-specific CAN objects XN300 slice modules
7.15 XN-322-7AI-U2PT
192
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
7.15.9 Module Diagnostic Messages (Object 0x3080)
Object 0x3080 contains status information on the module's general operat-
ing status.
Design of the data bytes:
Byte 0:
Sub-Index 1
≦
n
≦
254
Byte 1:
3 Byte
Byte 2
Sub index
1
≦
n
≦
254
B31
B30
B29
B28
B27
B26
B25
B24
B23
B22
B21
B20
B19
B18
B17
B16
MSB
LSB
Feature
Description / Value
EDS
Name
ModuleDiag
[MxSubExt3080]
ParameterName=ModuleDiag
ObjectType=0x7
DataType=0x0006
AccessType=ro
PDOMapping=1
Count=1
Description
Module Diagnostic Messages
Object Code
ARRAY
Mapping
PDO
Manual
Data type
UNSIGNED16
Sub index
01 … FE
hex
Access
ro
Default value
0000
hex
7
6
5
4
3
2
1
0
–
–
Data bit
Desig-
nation
Meaning
Notes
0
reserved
1
0 = sync OK
1 = no sync
2
0 = OK
1 = FLASH Data CRC Error
-
3
0 = OK
1 =RAM Data CRC Error
4
0 = OK
1 = EEProm version not valid
5-7
reserved