7 Product-specific CAN objects XN300 slice modules
7.19 XN-322-4AIO-U2
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
239
•
The global interrupt in object 0x6423 has been enabled with: TRUE.
Design of the data bytes:
7.19.6 Analog Input Interrupt Lower Limit Integer (Object 0x6425)
Object 0x6425 defines a lower limit and affects the transmission of object
0x6401 accordingly
Object 0x6401 will be transmitted (CAN transmission) if all of the following
conditions are met:
•
The analog input value (ENTRY into 0x6401) falls below the lower limit
(Lower Limit 0x6425).
•
Object 0x6421 is set to enable.
•
The global interrupt in object 0x6423 has been enabled with: TRUE.
Feature
Description / Value
EDS
Name
AI_UPPER_LIMIT
[MxSubExt6424]
ParameterName=AI_UPPER_LIMIT
ObjectType=0x7
DataType=0x0004
AccessType=rw
DefaultValue=0x00000000
PDOMapping=0
Count=2
Description
Analog Input Interrupt Upper Limit Integer
Object Code
ARRAY
Mapping
SDO
Data type
INTEGER32
Sub index
01 … FE
hex
Access
rw
1 Byte
Byte 0:
Sub index
1
≦
n
≦
254
B1
5
B1
4
B1
3
B1
2
B1
1
B1
0
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
MSB
LSB
4 Byte
3 Byte
Sub index
1
≦
n
≦
254
B31
B30
B29
B28
B27
B26
B25
B24
B23
B22
B21
B20
B19
B18
B17
B16
Not relevant
Not relevant
Summary of Contents for XN-312-GW-CAN
Page 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Page 4: ...II ...
Page 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Page 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Page 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...