7 Product-specific CAN objects XN300 slice modules
7.17 XN-322-10AI-TEKT
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
227
Byte 0:
Table 38:
Defining measuring ranges for analog inputs with the high and low data nibbles
Byte 0:
Sub index
1
≦
n
≦
254
B7
B6
B5
B4
B3
B2
B1
B0
MSB
LSB
AI2
AI1
AI4
AI3
AI6
AI5
AI8
AI7
Object
AI
Bit
Description
50A0
AI1
Bit 0-3
AI2
Bit 4-7
50A1
AI3
Bit 0-3
AI4
Bit 4-7
50A2
AI5
Bit 0-3
AI6
Bit 4-7
50A3
AI7
Bit 0-3
AI8
Bit 4-7
Hexadecimal
value
Part no.
Measuring range
Bit 0-3
Bit 4-7
0
hex
J
0 … +690 °C
1
hex
K
0…+940 °C
2
hex
T
0…+400 °C
3
hex
E
0…+520 °C
4
hex
N
0… +1080 °C
5
hex
S
0…+1760 °C
6
hex
R
0… +1760 °C
7
hex
B
0… +1820 °C
8
hex
L
0…+680 °C
9
hex
U
0…+590 °C