3 Commissioning
3.1 Take system bus into operation
40
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
3.1.1 Switching the gateway on with or without a config check
Figure 26:
Switching on the device with and without a config check
Switching the gateway on without a config check
If you want to put the gateway into operation without a config check, make
sure that the config check function is disabled:
▶
DIP switch 9 must be in the "OFF" position.
▶
Switch on the power supply.
The gateway will determine which I/O slice modules are currently on the sys-
tem bus and will store that configuration as the target configuration in its
device memory.
The I/O LED will flash green to indicate that the config check is disabled.
Switching the gateway on with a config check
If you want to put the gateway into operation with a config check, follow the
steps below:
Baud rate
OFF
ON
Yes
No
I/O LED green, continuous light
Switch on the device
Import target configuration
from device memory
DIP switch 9
Error on system bus
No errors on system bus
Store the actual configuration as
the target configuration
in the gateway's device memory
automatic detection / set fixed baud rate
Determine actual configura-
tion on system bus
I/O LED green, flashing
Device running
with config check
Device running
without config
Device stays
PRE-OPERATIONAL
Software-controlled RESET
I/O LED red, continuous light
Config check
Actu
al
Target
configuration
=
Summary of Contents for XN-312-GW-CAN
Page 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Page 4: ...II ...
Page 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Page 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Page 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...