7 Product-specific CAN objects XN300 slice modules
7.8 XN-322-8DO-P05
134
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
7.8.3 Input Voltage State (Object 0x3190)
Object 0x3190 contains status information on the module's supply voltage:
Bit 0: DC 24V, Output 1 to 8 OK
Design of the data bytes:
Byte 0:
Sub-Index 1
≦
n
≦
254
Feature
Description / Value
EDS
Name
InputVoltageState
[MxSubExt3190]
ParameterName=InputVoltageState
ObjectType=0x7
DataType=0x0005
AccessType=ro
PDOMapping=1
Count=1
Description
Status of supply voltage
Object Code
ARRAY
Mapping
PDO
Manual
Data type
UNSIGNED8
Sub index
01 … FE
hex
Access
ro
Default value
00
hex
Data bit
Designation
Meaning
Notes
0
Power supply, outputs 1–8:
0 = No power
1 = 24 V supply voltage OK at 1+
1-7
reserved