7 Product-specific CAN objects XN300 slice modules
7.10 XN-322-16DO-P05
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
141
7.10.2 Write Digital Output (Object 0x2050)
Object 0x2050 transmits the value of the channels' digital signal outputs in a
16-bit word.
Design of the data bytes:
Byte 0:
Sub index
1
≦
n
≦
254
B7
B6
B5
B4
B3
B2
B1
B0
MSB
LSB
Feature
Description / Value
EDS
Name
Output1_16
[MxSubExt2050]
Parameter-
Name=Output1_16
ObjectType=0x7
DataType=0x0006
AccessType=rww
PDOMapping=1
Count=1
Description
Write Digital Outputs
Object Code
VAR
Mapping
PDO
Data type
UNSIGNED16
Sub index
01 … FE
hex
Access
rww
Default value
0000
hex
1 Byte
Byte 0:
Sub index
1
≦
n
≦
254
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
MSB
LSB