7 Product-specific CAN objects XN300 slice modules
7.14 XN-322-4AI-PTNI
168
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
Default value
•
FALSE (0)
Object 0x6401 is not enabled and cannot transmit any analog input val-
ues.
•
TRUE (1)
Object 0x6401 is enabled and can transmit analog input values.
7.14.4 Analog Input Interrupt Upper Limit Integer (Object 0x6424)
Object 0x6424 defines an upper limit and affects the transmission of object
0x6401 accordingly
Object 0x6401 will be transmitted (CAN transmission) if all of the following
conditions are met:
•
The analog input value (ENTRY into 0x6401) is equal to or greater than
the upper limit (Upper Limit 0x6424).
•
Object 0x6421 is set to enable.
•
The global interrupt in object 0x6423 has been enabled with: TRUE.
Design of the data bytes:
Feature
Description / Value
EDS
Name
AnalogInputGlobalInterruptEnable
[MxFixed6423]
ParameterName=AnalogInputGlobalInterruptEnable
ObjectType=0x7
DataType=0x0001
AccessType=rw
DefaultValue=0
PDOMapping=0
Description
Analog Input Global Interrupt Enable
Object Code
Variable
Mapping
SDO
Data type
BOOLEAN
Access
rw
Default value
FALSE
Object Code
Variable
Feature
Description / Value
EDS
Name
AI_UPPER_LIMIT
[MxSubExt6424]
ParameterName=AI_UPPER_LIMIT
ObjectType=0x7
DataType=0x0004
AccessType=rw
DefaultValue=0x00000000
PDOMapping=0
Count=4
Description
Analog Input Interrupt Upper Limit Integer
Object Code
ARRAY
Mapping
SDO
Data type
INTEGER32
Sub index
01 … FE
hex
Access
rw
Default value
00000000
hex
Summary of Contents for XN-312-GW-CAN
Page 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Page 4: ...II ...
Page 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Page 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Page 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...