7 Product-specific CAN objects XN300 slice modules
7.2 XN-322-16DI-PD
110
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
7.2.1 Read Digital Input 8-Bit (Object 0x6000)
Object 0x6000 represents the digital value of the channels' digital input val-
ues. The object's data is automatically entered into the transmit PDOs
(default mapping).
Design of the data bytes:
7.2.2 Read Digital Inputs (Object 0x3140)
Object 0x3140 represents the channels' formatted digital input values in a
word.
0x4001
VISIBLE
STRING
SerialNumber
“6.2.8 Serial Number (Object
0x4001)”, page 78
–
const
SDO
0x4004
UNSIGNED8
UserLEDCon-
trol
User LED Control
“6.2.11 User LED Control
(Object 0x4004)”, page 81
–
rw
SDO
0x400C
VISIBLE
STRING
ProductName
Product Name
Name (Object 0x400C)”, page
82
–
ro
SDO
Index
(hex)
Data Type
Name
Function
Mapping
Access
Feature
Description / Value
EDS
Name
I-BYTE
[MxSubExt6000]
ParameterName=I-BYTE
ObjectType=0x7
DataType=0x0005
AccessType=ro
PDOMapping=1
Count=2
Description
Read Digital Input 8-Bit
Object Code
ARRAY
Mapping
PDO
Default
Data type
UNSIGNED8
Sub index
01 … FE
hex
Access
ro
Byte 0:
Sub index
1
≦
n
≦
254
B7
B6
B5
B4
B3
B2
B1
B0
MSB
LSB
Summary of Contents for XN-312-GW-CAN
Page 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Page 4: ...II ...
Page 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Page 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Page 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...