Table 12 . Contact I/O option module input ratings
Description
Rating
Minimum Detection Level:
10 V (ac rms or dc) (50 or 60 Hz)
(Using control-supplied whetting Voltage is recommended)
Maximum Applied Voltage:
250 Vac, rms, or 125 Vdc
Nominal Input Loading:
2 mA per input (internally current limited)
Typical Control Response Time:
50 msec (Note: Regulation tasks take priority over input activity.)
Minimum Input Pulse Time:
250 msec
Minimum Transition Time between Pulse Inputs:
250 msec
Input Protection:
Shunting type using MOVs and capacitors. Optical Isolation from input to system.
(1500 Vac, rms)
Hi-Pot Capability:
3.150 kV dc for 1 second, from one input set to the next or from one pin to
chassis, but not across the two terminals of a single input (due to MOVs).
Table 13 . Output ratings
Description
Rating
Maximum Switching Voltage:
250 Vac, rms or 125 Vdc
Maximum Switching Loading:
Refer to
Maximum Pickup Time:
8 msec (not including control response time)
Maximum Release Time:
15 msec (not including control response time)
Output Protection:
Shunting type using MOVs and capacitors. 1500 Vac, rms isolation between coil
and contacts
Hi-Pot Capability:
3.150 kV dc for 1 second from one output to the next or from one pin to chassis,
but not across two terminals of a single output (due to output protection).
Fusing:
Outputs are not internally fuse-protected. Customer-supplied fusing is
recommended.
10
5
2
1
0.5
0.2
0.1
10
20
50
100 200
500
Current (A)
Voltage (V)
Maximum Switching Power
AC Resistive Load
DC Resistive Load
AC Resistive Load:
DC Resistive Load:
Legend
Figure 53 . Maximum output switching graph
151
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS
MN225003EN April 2018
CL-7 Voltage Regulator Control