Table 10 . Function codes (continued)
Parameter
Unit of
Measure
Security Level
Default Value
Key Entry Limit
To Read
To Write
To Reset
Low
High
110 Tap Position
Sync Counter
XXXXX
MM-DD-YYYY HH:MM:SS
---
View
NA
Admin
Reset* to
0
NA
NA
•A count of the number of times the control tap position indication (TPI) was synchronized
either at neutral or when the regulator was able to tap up or down when TPI was at 16R or
16L respectively.
•This counter is reset by pressing ENTER and then ENTER again to confirm.
112 Percent
Regulation
XX.X %
%
View
NA
NA
NA
NA
NA
•This is the actual percentage that the regulator is actively boosting (raising) or bucking
(lowering) the input (source) voltage.
•When the regulator output voltage is greater than the input voltage (regulator boosting),
the sign is implied (+). When the output voltage is lower than the input voltage, the
sign is implied (-).
•Tap position indication is calculated as follows: % regulation = [(output/input) - 1] x 100.
•During reverse power operation, the control requires source voltage from a differential or
source potential transformer or from the source voltage calculation (see FC 39) to obtain
this parameter. Lack of this voltage will result in the parameter displaying dashes.
125 Energy kW-h
Forward
XXXX.X kW-h
KW-h
View
NA
Operate
Reset* to
0
NA
NA
•This is the total forward energy, measured in kilowatt hours.
•This is reset to zero by pressing ENTER and then ENTER again to confirm.
125 Energy kW-h
Reverse
XXXX.X kW-h
KW-h
View
NA
Operate
Reset* to
0
NA
NA
•This is the total reverse energy, measured in kilowatt hours.
•This is reset to zero by pressing ENTER and then ENTER again to confirm.
126 Energy kvar-h
Forward
XXXX.X kvar-h
Kvar-h
View
NA
Operate
Reset* to
0
NA
NA
•This is the total forward energy, measured in kvar.
•This is reset to zero by pressing ENTER and then ENTER again to confirm.
126 Energy kvar-h
Reverse
XXXX.X kvar-h
Kvar-h
View
NA
Operate
Reset* to
0
NA
NA
•This is the total reverse energy, measured in kvar.
•This is reset to zero by pressing ENTER and then ENTER again to confirm.
127 Maximum Percent
Regulation
XX.X %
MM-DD-YYYY HH:MM:SS
%
View
NA
Operate
Reset*
NA
NA
•This is the highest percentage that the regulator has raised the input voltage since last
reset.
•The control requires an input voltage from a differential or source potential transformer
to obtain this parameter. Lack of this voltage will result in the parameter displaying
dashes.
73
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS
MN225003EN April 2018
CL-7 Voltage Regulator Control