Table 10 . Function codes (continued)
Parameter
Unit of
Measure
Security Level
Default Value
Key Entry Limit
To Read
To Write
To Reset
Low
High
450 Alternate Config
Mode
Off
---
View
Modify
NA
Off
NA
NA
•This will turn on Alternate Configurations and designate a mode of operation. The options
are: Off; On; ARLH; ARLC; Config Logic; Enhanced ARLH; Enhanced ARLC.
•Selecting "On" will enable the basic Alternate Configuration settings selected at FC 452.
•See
Section 6: Control Features: Auto-restore local (ARL)
for more information on the ARL
settings.
•Selecting Config Logic will enable Alternate Configuration settings to be enabled or
disabled using configurable logic equations.
451 Alternate Config
State
Inactive
---
View
NA
NA
NA
NA
NA
•Displays the alternate configuration that is currently active. Display options include:
Alt Config 1 Active; Alt Config 2 Active; Alt Config 3 Active; ARLC Active; ARLH Active.
452 Alternate Config
Selection
Alt Config 1
---
View
Modify
NA
Off
NA
NA
•Allows for the selection of basic alternate configuration settings when FC 450 is set to
“On”. Options include: Alt Config 1; Alt Config 2; Alt Config 3; Config Logic.
453 ARL Timer
Period
XX Minutes
Minutes
View
Modify
NA
15
1
32767
•This sets the Auto Restore Local (ARL) time period.
•ARL is an alternate configurations feature that enables a control center to make changes
to the voltage regulator operation settings while actively communicating with the control.
When ARL is active, this parameter establishes the period in which a communications or
heartbeat signal must be received by the control to keep ARL active. If the signal is
not received, the control will revert back to the control settings locally stored.
460 Forward
Set Voltage
XXX.X Volts
Volts
View
Modify
NA
120.0
100.0
135.0
•Forward Set Voltage for Alternate Configuration 1.
461 Forward
Bandwidth
X.X Volts
Volts
View
Modify
NA
2.0
1.0
6.0
•Forward Bandwidth for Alternate Configuration 1.
462 Forward
Time Delay
XXX Seconds
Seconds
View
Modify
NA
45
5
180
•Forward Time Delay for Alternate Configuration 1.
463 Fwd Line Drop
Comp. Resistance
XX.X Volts
Volts
View
Modify
NA
0.0
-96.0
96.0
•Forward Line Drop Compensation Resistance for Alternate Configuration 1.
464 Fwd Line Drop
Comp. Reactance
XX.X Volts
Volts
View
Modify
NA
0.0
-96.0
96.0
•Forward Line Drop Compensation Reactance for Alternate Configuration 1.
86
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS
MN225003EN April 2018
CL-7 Voltage Regulator Control