Table 10 . Function codes (continued)
Parameter
Unit of
Measure
Security Level
Default Value
Key Entry Limit
To Read
To Write
To Reset
Low
High
076 # of Pulse
Reduction Steps
XX
---
View
Modify
NA
0
0
10
•Up to ten steps of remotely activated voltage reduction are available. The voltage
reduction steps are activated when FC 70 is set to Remote/Pulse and a momentary pulse is
applied to the appropriate input terminal.
•FC 76 defines the number of steps selected for pulsed voltage reduction. The percentage of
voltage reduction of each step is defined at FC 77.
•See
Section 6: Control Features: Analog SCADA
•If an alternate configuration is active, the fourth LCD line displays which one is active,
e.g. (ALT CONFIG 1).
077 % of Voltage Red
Per Pulse Step
XX.X %
%
View
Modify
NA
0.0
0.0
10.0
•This defines the percentage of voltage reduction which will be applied for each step of
pulsed voltage reduction selected at FC 76.
•See
Section 6: Control Features: Analog SCADA
•If an alternate configuration is active, the fourth LCD line displays which one is active,
e.g. (ALT CONFIG 1).
078 Present Voltage
Reduction Step
XX
---
View
NA
NA
NA
NA
NA
•Displays the current step when Remote/Pulse voltage reduction is active.
•If alternate configuration is active, the fourth LCD line displays which one is active,
i.e. (ALT CONFIG 1).
079 SOFT-ADD-AMP
Limits
Off
---
View
Modify
NA
Off
NA
NA
•This parameter enables the Soft ADD-AMP feature. Options include: Off; On; Remote
Override; Cfg Logic Active; Adaptive.
•See
Section 6: Control Features: Soft ADD-AMP feature
•If an alternate configuration is active, the fourth LCD line displays which one is active,
e.g. (ALT CONFIG 1).
080 Voltage Limiter
Mode
Off
---
View
Modify
NA
Off
NA
NA
•The control has voltage-limiting capabilities for both high-voltage and low-voltage
conditions. Options include: Off; High limit only; High/low limits; IVVC High Limit Only;
IVVC High/Low Limits.
•See
Section 6: Control Features: Voltage limiter
.
•If an alternate configuration is active, the fourth LCD line displays which one is active,
e.g. (ALT CONFIG 1)
67
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS
MN225003EN April 2018
CL-7 Voltage Regulator Control